Detected condition and possible cause
Detected condition |
Possible cause |
Cooling fan relay signal is not input to ecm. |
|
Wiring diagram
Troubleshooting
Caution when using the multi-circuit tester, do not strongly touch the terminal of the ecm coupler with a needle pointed tester probe to prevent terminal damage. |
Note after repairing the trouble, clear the dtc using sds tool. Refer to “use of sds diagnosis reset procedures” . |
Step |
Action |
Yes |
No |
1 |
Is the cooling fan relay ok? |
|
Replace the cooling fan relay with a new one. |
Active control inspection
At this time, if an operation sound is heard from the cooling fan relay and cooling fan motors are operated, the function is normal.
Note the cooling fan relay and cooling fan motor inspection is operational at any engine coolant temperature until reaching 100 °c (212 °f). In a hot engine condition with the intake air temperature exceeding 40 °c (104 °f), however, the engine coolant temperature at which the inspection is operational will be restricted to 95 °c (203 °f). |
Note
|
Front wheel related parts inspection
Refer to “front wheel assembly removal and installation” .
Tire
Refer to “tire inspection” in section 0b .
Front brake disc
Refer to “front brake disc inspection” in section 4b .
Dust seal
Inspect the lip of dust seals for wear or damage. If any
defects are found, replace the dust seal ...
Steering damper maintenance
Keep the steering damper
shaft 1 clean at all times.
Wipe off any oil residue with a
cloth.
Do not confuse the grease-like
residue on the steering damper's
shaft with an oil leak. Collection of
this residue is normal and is from
oil seal lubricant used in the
damper.
Yo ...
Evaporative emission control system
diagram (only for e-33)
Fuel tank
Fuel-vapor separator
Fuel pump
Fuel feed hose
Fuel shut-off valve
Iap sensor
Surge hose
Evap canister
Purge hose
Evap system purge control solenoid valve
Fue
Hc vapor
Fresh air
Vacuum
...