Detected condition and possible cause
|
Detected condition |
Possible cause |
| Cooling fan relay signal is not input to ecm. |
|
Wiring diagram

Troubleshooting
| Caution when using the multi-circuit tester, do not strongly touch the terminal of the ecm coupler with a needle pointed tester probe to prevent terminal damage. |
| Note after repairing the trouble, clear the dtc using sds tool. Refer to “use of sds diagnosis reset procedures” . |
|
Step |
Action |
Yes |
No |
|
1 |
Is the cooling fan relay ok? |
|
Replace the cooling fan relay with a new one. |
Active control inspection

At this time, if an operation sound is heard from the cooling fan relay and cooling fan motors are operated, the function is normal.
| Note the cooling fan relay and cooling fan motor inspection is operational at any engine coolant temperature until reaching 100 °c (212 °f). In a hot engine condition with the intake air temperature exceeding 40 °c (104 °f), however, the engine coolant temperature at which the inspection is operational will be restricted to 95 °c (203 °f). |


Note
|

DTC “c49” (p1656): pair control solenoid
valve circuit malfunction
DTC “c62” (p0443): evap system purge
control solenoid valve circuit malfunction
(e-33 only)DTC “c46” (p1657-h/l or p1658): excv
actuator circuit malfunction
Detected condition
Possible cause
C46
The operation signal does not reach the
excv actuator.
Excva position sensor voltage low or
high
0.14 V ≤ Sensor voltage < 4.9 V
(without the above range)
excva can not operate properly.
Excva ...
Special tools and equipment
Special tool
...
Special tools and equipment
Recommended service material
Note
required service material is also described in the following.
“Rear brake components”
Special tool
...