Detected condition and possible cause
Detected condition |
Possible cause |
Cooling fan relay signal is not input to ecm. |
|
Wiring diagram
Troubleshooting
Caution when using the multi-circuit tester, do not strongly touch the terminal of the ecm coupler with a needle pointed tester probe to prevent terminal damage. |
Note after repairing the trouble, clear the dtc using sds tool. Refer to “use of sds diagnosis reset procedures” . |
Step |
Action |
Yes |
No |
1 |
Is the cooling fan relay ok? |
|
Replace the cooling fan relay with a new one. |
Active control inspection
At this time, if an operation sound is heard from the cooling fan relay and cooling fan motors are operated, the function is normal.
Note the cooling fan relay and cooling fan motor inspection is operational at any engine coolant temperature until reaching 100 °c (212 °f). In a hot engine condition with the intake air temperature exceeding 40 °c (104 °f), however, the engine coolant temperature at which the inspection is operational will be restricted to 95 °c (203 °f). |
Note
|
Diagnostic information and procedures
Starting system symptom diagnosis
Condition
Possible cause
Correction / reference item
Engine does not turn
though the starter motor
runs
Faulty starter clutch.
Replace.
Starter button is not
effective
Run down battery
Repair or replac ...
Oil pressure regulator / oil strainer
inspection
Refer to “oil pan / oil pressure regulator / oil strainer removal and
installation” .
Oil pressure regulator
Inspect the operation of the oil pressure regulator by
pushing the piston with a proper bar.
If the piston does not operate smoothly, replace the oil
pressure regulator with a new on ...
Ignition switch
The ignitionr switch has 4 positions:
"Off" position
All electrical circuits are cut off.
The engine will not start. The key
can be removed.
"On" position
The ignition circuit is completed
and the engine can run. The
headlight and taillight will automatically
turn ...